18th Edition Mock

🌩️ Protection Against Voltage Disturbances and SPDs (Part 4, Chapter 44)

Protection Against Voltage Disturbances and SPDs (Part 4, Chapter 44)

Chapter 44 of BS 7671:2018+A2:2022 addresses protection against voltage and electromagnetic disturbances. It is divided into Section 442 (faults between high-voltage and low-voltage systems), Section 443 (transient overvoltages of atmospheric origin or due to switching), Section 444 (electromagnetic disturbances) and Section 445 (undervoltage).

Under Regulation 443.4, protection against transient overvoltages must be provided where the consequence of overvoltage could result in serious injury to, or loss of, human life; interruption of public services and/or damage to cultural heritage; interruption of commercial or industrial activity; or could affect a large number of co-located individuals. This consequence-based approach replaced the Calculated Risk Level (CRL) method, which was removed in Amendment 2. For all other cases (notably single dwellings), a risk assessment determines whether SPD protection is required; protection may be omitted where the total value of the installation and equipment does not justify it, but the decision and acceptance of the risk rests with the installation owner.

Equipment must have a rated impulse withstand voltage (Uw) not less than the value for its overvoltage category in Table 443.2. For a 230/400 V supply these are:

Section 534 governs the selection and erection of surge protective devices (SPDs). Type 1 SPDs are installed at the origin and tested with a 10/350 us lightning current impulse (Iimp), suiting buildings with lightning protection or overhead supplies. Type 2 SPDs sit at distribution boards, tested with the nominal discharge current In (8/20 us waveform). Type 3 SPDs are fitted near sensitive terminal equipment, only as a supplement to Type 2 (never alone), tested with a 1.2/50 and 8/20 us combination wave.

The SPD's voltage protection level (Up) must be lower than the equipment Uw (Up < Uw), and not greater than 2.5 kV for a 230/400 V installation. The total connecting lead length should not exceed 0.5 m to preserve protection. Coordination of multiple SPDs (Regulation 534.4.4.5) must follow the manufacturer's instructions, and a backup overcurrent device must be provided so an end-of-life SPD failure does not create a fire or shock hazard.

Section 444 requires measures against electromagnetic disturbances (EMI/EMC), including appropriate bonding networks and adequately sized earthing/equipotential conductors, especially with IT equipment. Section 445 requires precautions against undervoltage where a reduction, loss or restoration of voltage could cause danger to persons or property or damage equipment.

Practise the full mock test for free

Sample questions (35)

1. Within Chapter 44 of BS 7671, which Section specifically deals with protection against transient overvoltages of atmospheric origin or due to switching?

  1. Section 442
  2. Section 443
  3. Section 444
  4. Section 445

Section 443 covers transient overvoltages of atmospheric origin or due to switching; 442 covers HV/LV faults, 444 electromagnetic disturbances and 445 undervoltage. (BS 7671:2018+A2:2022, Part 4, Chapter 44 (Section 443))

2. Which Section of Chapter 44 of BS 7671 addresses protection against undervoltage?

  1. Section 443
  2. Section 444
  3. Section 445
  4. Section 534

Section 445 covers protection against undervoltage, where loss of voltage and subsequent restoration could cause danger or damage. (BS 7671:2018+A2:2022, Section 445)

3. Under Regulation 443.4, in which of the following situations is protection against transient overvoltages always required?

  1. Where overvoltage could result in serious injury to, or loss of, human life
  2. Where the building is a single-family dwelling of modest value
  3. Where only portable hand tools are used on the circuits
  4. Where the supply is taken from an underground cable network only

Regulation 443.4 requires SPD protection where the consequence of overvoltage could result in serious injury to or loss of human life, among other listed consequences. (BS 7671:2018+A2:2022, Regulation 443.4)

4. For a single dwelling that does not fall under the mandatory consequence criteria, how is the need for SPD protection determined under BS 7671?

  1. It is always mandatory regardless of the dwelling
  2. It is determined by a risk assessment, with the owner accepting any decision to omit it
  3. It is decided solely by the distribution network operator
  4. It is never permitted in a single dwelling

For other cases such as single dwellings, a risk assessment determines whether SPDs are needed; protection may be omitted, but the owner accepts the risk. (BS 7671:2018+A2:2022, Regulation 443.4/443.5)

5. What significant change to the assessment of transient overvoltage protection was introduced in Amendment 2 (BS 7671:2018+A2:2022)?

  1. The Calculated Risk Level (CRL) method was removed and replaced by consequence-based criteria
  2. SPDs became prohibited in domestic installations
  3. Type 3 SPDs were reclassified as Type 1
  4. The 230/400 V impulse withstand values were doubled

Amendment 2 removed the complex Calculated Risk Level (CRL) method and replaced it with the consequence-based criteria of Regulation 443.4. (BS 7671:2018+A2:2022 (IET Wiring Matters on A2 changes))

6. For a nominal 230/400 V supply, what is the rated impulse withstand voltage (Uw) for equipment at the origin of the installation (Overvoltage Category IV)?

  1. 1.5 kV
  2. 2.5 kV
  3. 4 kV
  4. 6 kV

Table 443.2 gives 6 kV for Category IV (origin of installation) at a nominal 230/400 V supply. (BS 7671:2018+A2:2022, Table 443.2)

7. For a 230/400 V installation, what rated impulse withstand voltage corresponds to Overvoltage Category II equipment such as appliances and loads?

  1. 1.5 kV
  2. 2.5 kV
  3. 4 kV
  4. 6 kV

Category II (appliances/loads) has a rated impulse withstand voltage of 2.5 kV per Table 443.2 for a 230/400 V supply. (BS 7671:2018+A2:2022, Table 443.2)

8. In a 230/400 V installation, which rated impulse withstand voltage applies to Overvoltage Category III equipment used in distribution circuits?

  1. 1.5 kV
  2. 2.5 kV
  3. 4 kV
  4. 6 kV

Category III (distribution circuits) equipment has a rated impulse withstand voltage of 4 kV per Table 443.2. (BS 7671:2018+A2:2022, Table 443.2)

9. Specially protected equipment with a particularly low rated impulse withstand voltage, such as certain electronic devices, falls into which overvoltage category for a 230/400 V supply, and at what value?

  1. Category I at 1.5 kV
  2. Category II at 2.5 kV
  3. Category III at 4 kV
  4. Category IV at 6 kV

Category I covers specially protected equipment with a rated impulse withstand voltage of 1.5 kV at 230/400 V per Table 443.2. (BS 7671:2018+A2:2022, Table 443.2)

10. Electrical equipment installed in a 230/400 V installation must have a rated impulse withstand voltage (Uw) that is which of the following relative to the value given for its overvoltage category in Table 443.2?

  1. Not less than the tabulated value
  2. Exactly equal to half the tabulated value
  3. Not more than the tabulated value
  4. Independent of the tabulated value

Equipment must have a rated impulse withstand voltage not less than the value given for its overvoltage category in Table 443.2. (BS 7671:2018+A2:2022, Table 443.2)

11. Where in an installation is a Type 1 SPD typically installed?

  1. At the origin of the installation
  2. Within a 13 A plug top
  3. Close to sensitive terminal equipment only
  4. Inside the final luminaire of each circuit

Type 1 SPDs are installed at the origin of the installation to handle direct or partial lightning currents. (BS 7671:2018+A2:2022, Section 534; IEC 61643 Class I)

12. Type 1 SPDs are tested and classified using which lightning current impulse waveform?

  1. 8/20 microsecond nominal discharge current
  2. 10/350 microsecond lightning current impulse
  3. 1.2/50 microsecond voltage wave
  4. 50/60 Hz power-frequency current

Type 1 SPDs are tested with a 10/350 microsecond lightning current impulse (Iimp), the IEC 61643 Class I test. (BS 7671:2018+A2:2022, Section 534; IEC 61643 Class I test)

13. Type 2 SPDs are most commonly installed at which location to protect against switching and residual lightning overvoltages?

  1. At distribution boards
  2. At the consumer's outdoor lightning rod
  3. Within the cable to the meter only
  4. At the supply transformer on the network

Type 2 SPDs are installed at distribution boards to protect against switching and residual lightning overvoltages. (BS 7671:2018+A2:2022, Section 534; IEC 61643 Class II)

14. Which test waveform is used to classify a Type 2 SPD's nominal discharge current (In)?

  1. 10/350 microsecond waveform
  2. 8/20 microsecond waveform
  3. 1.2/50 microsecond waveform
  4. 250/2500 microsecond waveform

Type 2 SPDs are classified using the nominal discharge current In with an 8/20 microsecond waveform (IEC 61643 Class II test). (BS 7671:2018+A2:2022, Section 534; IEC 61643 Class II test)

15. Which statement about Type 3 SPDs is correct?

  1. They are installed at the origin to carry direct lightning currents
  2. They may be used alone as the sole means of overvoltage protection
  3. They are installed close to sensitive terminal equipment and only supplement a Type 2 SPD
  4. They are tested with a 10/350 microsecond impulse

Type 3 SPDs are fitted close to sensitive equipment and are only used as a supplement to a Type 2 SPD, never on their own. (BS 7671:2018+A2:2022, Section 534; IEC 61643 Class III)

16. Type 3 SPDs are tested and classified using which form of test wave?

  1. A 10/350 microsecond lightning current impulse
  2. A combination (hybrid) 1.2/50 microsecond voltage and 8/20 microsecond current wave
  3. A pure 50 Hz power-frequency overvoltage
  4. A 250/2500 microsecond switching impulse

Type 3 SPDs use a combination/hybrid wave of 1.2/50 microsecond voltage and 8/20 microsecond current (IEC 61643 Class III test). (BS 7671:2018+A2:2022, Section 534; IEC 61643 Class III test)

17. A building has a structural lightning protection system and is fed by overhead lines. Which SPD type should be installed at the origin to handle the risk of direct or partial lightning currents?

  1. Type 3 only
  2. Type 2 only
  3. Type 1
  4. No SPD is needed in this case

A Type 1 SPD is required at the origin for buildings with a lightning protection system or fed by overhead lines at risk of direct/partial lightning currents. (BS 7671:2018+A2:2022, Section 534; IEC 61643 Class I)

18. Which Section of BS 7671 covers the selection and erection of SPDs, including their type, coordination, location and connection?

  1. Section 443
  2. Section 444
  3. Section 445
  4. Section 534

Section 534 covers the selection and erection of SPDs for protection against transient overvoltages. (BS 7671:2018+A2:2022, Section 534)

19. To ensure coordination of protection, how must the SPD's voltage protection level (Up) relate to the rated impulse withstand voltage (Uw) of the equipment it protects?

  1. Up must be higher than Uw
  2. Up must equal Uw exactly
  3. Up must be lower than Uw
  4. Up is unrelated to Uw

The SPD must be selected so that its voltage protection level Up is lower than the equipment's rated impulse withstand voltage Uw (Up < Uw). (BS 7671:2018+A2:2022, Section 534 / Regulation 534.4.4)

20. For protection against transient overvoltages of atmospheric origin in a 230/400 V installation, the SPD voltage protection level Up should be selected to be no greater than which value?

  1. 1.5 kV (Category I)
  2. 2.5 kV (Category II)
  3. 4 kV (Category III)
  4. 6 kV (Category IV)

Up should be selected to be not greater than the Category II rated impulse withstand voltage of 2.5 kV for a 230/400 V installation. (BS 7671:2018+A2:2022, Section 534 with Table 443.2)

21. When an SPD is connected at the origin to protect equipment within the installation, what is the recommended maximum total lead length of the connecting conductors to preserve the effective protection level?

  1. 0.5 metres
  2. 1.5 metres
  3. 3 metres
  4. No limit applies

The total lead length of the SPD connecting conductors should not exceed 0.5 metres to minimise additional volt drop and preserve protection. (BS 7671:2018+A2:2022, Regulation 534.4.4.4 / 534.4.10)

22. Why must a backup overcurrent protective device be provided with an SPD in accordance with the manufacturer's instructions?

  1. To increase the SPD's discharge current rating
  2. To ensure an end-of-life SPD failure does not create a fire or shock hazard
  3. To allow the SPD to function without earthing
  4. To convert a Type 2 SPD into a Type 1 SPD

A backup overcurrent device (fuse or circuit-breaker) is required so that an end-of-life SPD failure does not create a fire or shock hazard. (BS 7671:2018+A2:2022, Regulation 534.4.1 / 534.4.6)

23. Under Regulation 443.4 of BS 7671, which of the following is one of the consequences that requires protection against transient overvoltages to be provided?

  1. Where overvoltage could result in serious injury to, or loss of, human life
  2. Where the installation uses more than three final circuits
  3. Where the supply is fed by an underground cable only
  4. Where the building is less than ten years old

Regulation 443.4 requires SPD protection where a transient overvoltage could result in serious injury to, or loss of, human life, among other listed consequences. (BS 7671:2018+A2:2022, Regulation 443.4)

24. Which chapter of BS 7671 deals with protection against voltage disturbances and electromagnetic disturbances?

  1. Chapter 41
  2. Chapter 44
  3. Chapter 53
  4. Chapter 54

Chapter 44 of Part 4 covers protection against voltage disturbances and electromagnetic disturbances, including Sections 442, 443, 444 and 445. (BS 7671:2018+A2:2022, Part 4, Chapter 44)

25. Which section of Chapter 44 specifically addresses transient overvoltages of atmospheric origin or due to switching?

  1. Section 442
  2. Section 443
  3. Section 444
  4. Section 445

Section 443 deals with protection against transient overvoltages of atmospheric origin or due to switching; Section 445 covers undervoltage. (BS 7671:2018+A2:2022, Part 4, Chapter 44)

26. A hospital's electrical installation is being designed. Under Regulation 443.4, what is the correct approach to transient overvoltage protection?

  1. No SPD is needed because the hospital has a standby generator
  2. Protection must be provided because loss of supply could result in serious injury to, or loss of, human life
  3. A risk assessment may be used to omit protection if equipment is inexpensive
  4. SPDs are only required if the hospital is fed by overhead lines

Where consequences could result in serious injury to or loss of human life, such as in a hospital, Regulation 443.4 requires that protection against transient overvoltages be provided. (BS 7671:2018+A2:2022, Regulation 443.4)

27. For a single domestic dwelling not falling under the mandatory consequence categories, how is the need for SPD protection determined under BS 7671?

  1. SPDs are never required in dwellings
  2. A risk assessment determines whether SPD protection is required
  3. SPDs are always mandatory in every dwelling
  4. The decision is made solely by the distribution network operator

For cases such as single dwellings outside the listed consequences, a risk assessment determines whether SPD protection is required, with the owner accepting the residual risk. (BS 7671:2018+A2:2022, Regulation 443.4/443.5)

28. Following a risk assessment, the designer concludes SPD protection could be omitted for a small dwelling. Where does responsibility for accepting that risk ultimately rest?

  1. With the distribution network operator
  2. With the manufacturer of the consumer unit
  3. With the installation owner
  4. With the building control body

Protection may be omitted where the value of the installation does not justify it, but the decision and acceptance of the risk rests with the installation owner. (BS 7671:2018+A2:2022, Regulation 443.4/443.5)

29. According to Regulation 443.4, transient overvoltage protection must be provided where the consequence could result in which of the following?

  1. Interruption of commercial or industrial activity
  2. A slight increase in the electricity bill
  3. A momentary flicker of lighting only
  4. Minor inconvenience to a single occupant

One of the listed consequences in Regulation 443.4 requiring protection is the interruption of commercial or industrial activity. (BS 7671:2018+A2:2022, Regulation 443.4)

30. Which of the following is listed in Regulation 443.4 as a consequence requiring protection against transient overvoltages?

  1. Interruption of public services and/or damage to cultural heritage
  2. Increased standing charge on the energy tariff
  3. The need to replace a single light bulb
  4. A temporary dip in Wi-Fi performance

Regulation 443.4 lists interruption of public services and/or damage to cultural heritage as a consequence requiring SPD protection. (BS 7671:2018+A2:2022, Regulation 443.4)

31. A large open-plan office shared by several hundred employees is being assessed. Which Regulation 443.4 criterion is most directly relevant to requiring SPD protection here?

  1. The fact that the building is rented rather than owned
  2. The consequence affecting a large number of co-located individuals
  3. The age of the wiring installation
  4. The colour of the cable insulation used

Regulation 443.4 requires protection where the consequence could affect a large number of co-located individuals, as in a large shared workplace. (BS 7671:2018+A2:2022, Regulation 443.4)

32. For a nominal 230/400 V supply, what is the rated impulse withstand voltage (Uw) for Category IV equipment at the origin of the installation in Table 443.2?

  1. 1.5 kV
  2. 2.5 kV
  3. 4 kV
  4. 6 kV

Table 443.2 gives 6 kV for Category IV (origin of installation) at a nominal 230/400 V supply. (BS 7671:2018+A2:2022, Table 443.2)

33. An item of equipment is classed as Category II (an appliance or current-using load) on a 230/400 V system. What minimum rated impulse withstand voltage (Uw) should it have per Table 443.2?

  1. 1.5 kV
  2. 2.5 kV
  3. 4 kV
  4. 6 kV

Table 443.2 assigns 2.5 kV to Category II equipment (appliances/loads) on a nominal 230/400 V supply. (BS 7671:2018+A2:2022, Table 443.2)

34. In Table 443.2 for a 230/400 V installation, which overvoltage category has the rated impulse withstand voltage of 4 kV?

  1. Category I (specially protected equipment)
  2. Category II (appliances/loads)
  3. Category III (distribution circuits)
  4. Category IV (origin of installation)

Category III (distribution circuits) has a rated impulse withstand voltage of 4 kV per Table 443.2. (BS 7671:2018+A2:2022, Table 443.2)

35. Which section of BS 7671 covers the selection and erection of SPDs for protection against transient overvoltages?

  1. Section 443
  2. Section 445
  3. Section 534
  4. Section 411

Section 534 covers the selection and erection of SPDs, addressing type, coordination, location and connection. (BS 7671:2018+A2:2022, Section 534)

Start free